5.59.23.53.522.0CESCGeneratoror PN3/410.256.8All Measurmentsin Inches19.514.7Pads can either be poured on site, or precast by Alpha Technologies. The
2.2 Utility Power ConnectionCAUTION: The “Utility Power Connection” procedure must ONLY be performed by qualifiedservice personnel and in compliance
240VAC Service (XM Series 2 915-240 Power Supply; XM Series 2 922-48 for UPE-4 and UPE-8): Enclosures used with the XMSeries 2 915-240 or 922-48 are e
ONOFFNeutralLine 1GroundFrom UtilityTo EnclosureTo Ground Rod240 VACService Entrance120 VACService Entrance2.2 Utility Power Connection, continuedONO
OFF20ONGroundLine 2Neutralline 1OFFONGroundNeutralline 12.2 Utility Power Connection, continued240 VAC Meter Base120 VAC Meter Base2. Installation14
GeneratorEnclosureSide WallSidecarEnclosureBack WallDC Output From GeneratorLineNeutralGroundPositiveNegative120 VAC From Service EntranceECM Interfac
Input Power Panel (IPP)SPIEnclosureGrounding RailThe Sidecar enclosure contains an Input Power Panel (IPP), one or two Service Power Inserters(SPI),an
4312312Upper ShelfLower Sheff48 VoltBattery PackBCK P/N 874-665-2036 VoltBattery PackBCK P/N 874-664-202.5 Battery Pack Wiring2. Installation17 031-1
2.6 Power Supply Placement1. Place the XM2 power supply onto the top shelf of the side car.2. Verify that the AC Input Breaker in the service entrance
2.7 Battery Remote Temperature Sensor (RTS)Tools Needed:Adhesive TapeProcedure:For enclosures with multiple battery strings, the RTS must be locatedwi
PowerAlpha Technologies®
2.8 Service Power Inserter1. The SPI box(es) are mounted on the shelfsupport bracket.2. Remove the two screws on the face of theSPI and lift off the c
Due to continuing product improvements, Alpha reserves the right to change specifications without notice.Copyright © 2004 by Alpha Technologies, Inc.
CE SidecarEnclosure Installation Manual031-106-C1-001, Rev. AEffective Date: March, 2004Copyright© 2004Alpha Technologies, Inc.NOTE: Photographs conta
TMTable of Contents1. Introduction ... 92. Installation ...
MECHANICAL OR MOVING PARTS HAZARDThese symbols indicate the presence of a “mechanical or moving partshazard” in this area of the product. Use caution
A “Warning” identifies conditions and actions that pose a hazard to the user.A “Caution” identifies conditions and actions that may damage the powersu
Lead-acid batteries contain dangerous voltages, currents and corrosive material. Batteryinstallation, maintenance, service and replacement must be per
Important Installation NotesSave these instructions for future referenceThe system must be installed ONLY by qualified service personnel.Consult local
The CESC enclosure is a cost effective 'all in one' power system. The side car provides for asingle power module, batteries, and generator i