AlphaGen DCX2000 36VDC Portable GeneratorOperation ManualEffective: July 2013
10 041-135-B0-001 Rev. A (07/2013)2.0 Operation, continued2.2 Fuel LevelGasoline is extremely ammable and can be explosive. Refuel in a well-ventil
11041-135-B0-001 Rev. A (07/2013)2.0 Operation, continued2.3 Air CleanerNever run the engine without the air cleaner element in place. Rapid engine
12 041-135-B0-001 Rev. A (07/2013)2.4 Power System Connections2.4.1 Y-Style ConnectionFig. 2-4, Y-Style Connection213F us eALM/RDYRSTFLASH = MIN ALM
13041-135-B0-001 Rev. A (07/2013)Fig. 2-5, Ring Lug Style Connection2.4 Power System Connections, continued2.4.2 Ring Lug Style Connection2.0 Opera
14 041-135-B0-001 Rev. A (07/2013)2.4 Power System Connections, continued2.4.3 Alligator Clamp Style Connection2.0 Operation, continuedREDBLACK213F
15041-135-B0-001 Rev. A (07/2013)2.5 Start-UpBefore starting the engine, verify the output circuit breaker is in the OFF position.Procedure:1. Connec
16 041-135-B0-001 Rev. A (07/2013)2.0 Operation, continued2.6 Operation at High AltitudeThe standard carburetor air-fuel mixture will be excessively
17041-135-B0-001 Rev. A (07/2013)2.0 Operation, continued2.9 Output, Alarm and Oil LEDsBefore connecting or reconnecting a power supply to the gener
18 041-135-B0-001 Rev. A (07/2013)3.0 ServicingThe maintenance schedule (Section 3.2, Maintenance Schedule) maintains the generator in peak operating
19041-135-B0-001 Rev. A (07/2013)3.0 Servicing, continued3.1 Emission Control System, continuedReplacement Parts and AccessoriesThe parts making up
Safety NotesReview the drawings and illustrations contained in this manual before proceeding. If there are any questions regarding the safe installati
20 041-135-B0-001 Rev. A (07/2013)3.2 Maintenance ScheduleItemMaintenance ProcedureRegular Service period. Perform at every indicated month or operat
21041-135-B0-001 Rev. A (07/2013)3.0 Servicing, continued3.3 Changing OilEngine oil is HOT! Avoid contact with skin and clothing.WARNING! BURN HAZAR
22 041-135-B0-001 Rev. A (07/2013)3.4 Air Cleaner ServiceDo not use gasoline or low ash point solvents for cleaning. They are ammable and explosive
23041-135-B0-001 Rev. A (07/2013)3.0 Servicing, continued3.5 Spark Plug MaintenanceTo ensure proper engine operation, the spark plug must be in good
24 041-135-B0-001 Rev. A (07/2013)Fig. 3-5, Accessing the Spark ArrestorSpark ArrestorM6 ScrewsMufer GrillM4 Screws3.0 Servicing, continued3.6 Spar
25041-135-B0-001 Rev. A (07/2013)4.0 Transport and Storage Instructions4.1 Transporting the GeneratorWhen transporting the generator, it should alwa
26 041-135-B0-001 Rev. A (07/2013)Fig. 4-1, Starter Grip4.0 Transport and Storage Instructions, continued4.4 Long Term StorageGasoline is extremely
27041-135-B0-001 Rev. A (07/2013)Fig. 5-1, Replace Spark PlugSpark Plug Cap5.0 TroubleshootingDescription of Problem Corrective ActionEngine will not
28 041-135-B0-001 Rev. A (07/2013)6.0 SpecicationsDCX2000 Portable Generator SpecicationsGeneratorModel DCX2000-36Rated Voltage (VDC) 39.5Rated Cur
29041-135-B0-001 Rev. A (07/2013)7.0 Warranty Information7.1 California Emissions Control Warranty StatementWarranty Rights and ObligationsThe Calif
3041-135-B0-001 Rev. A (07/2013)AlphaGen DCX200036VDC Portable Generator Operation Manual041-135-B0-001, Rev. AEffective Date: July 2013Copyright 2013
30 041-135-B0-001 Rev. A (07/2013)7.0 Warranty Information, continued7.2 Emission Control System WarrantyThe generator engine complies with U.S. Env
Visit us at www.alpha.comAlpha Technologies Inc.3767 Alpha WayBellingham, WA 98226 United StatesTel: +1 360 647 2360Fax: +1 360 671 4936Alpha Technolo
4 041-135-B0-001 Rev. A (07/2013)Table of ContentsDCX2000 Portable Generator Safety Notes ...
5041-135-B0-001 Rev. A (07/2013)Figures & TablesFig. 1-1, DCX2000 Generator Components ...
6 041-135-B0-001 Rev. A (07/2013)DCX2000 Portable Generator Safety NotesThe manufacturer cannot anticipate every circumstance that may involve a hazar
7041-135-B0-001 Rev. A (07/2013)1.0 IntroductionThe Alphagen DCX2000 portable DC generator supplies DC voltage to a power supply battery bus when comm
8 041-135-B0-001 Rev. A (07/2013)1.0 Introduction, continued1.1 DCX2000 Generator Components, continuedThe engine serial number is stamped on the en
9041-135-B0-001 Rev. A (07/2013)2.1 Oil LevelPower OFF the generator engine and place on a level surface before servicing.WARNING! ELECTRICAL HAZARD•