AlphaNet™ IDH4 Series DOCSIS® Status Monitor for the XM3-HP CableUPS®Technical ManualEffective: November 2013
10746-257-B5-001, Rev. A1 (11/2013)All power supply data is stored in the power supply inverter module's class information base (CIB) tables in t
11746-257-B5-001, Rev. A1 (11/2013)The IDH4 Series cable modem must be recognized by the CMTS as a valid device to be assigned an IP address from the
12746-257-B5-001, Rev. A1 (11/2013)The above diagram, read left to right, indicates the order of operations as the transponder comes online. There are
13746-257-B5-001, Rev. A1 (11/2013)3.0 Network Conguration3.1 Provisioning the DHCP Server with the MAC AddressesOn the DHCP server, assign the cab
14746-257-B5-001, Rev. A1 (11/2013)3.2.1 Setting Modem Community StringsSet the modem community strings with the DOCSIS Conguration File by includin
15746-257-B5-001, Rev. A1 (11/2013)MIB Parameter Object ID Description ValuedocsDevNmAccessIP 1.3.6.1.2.1.69.1.2.1.2.x IP address of trap destination,
16746-257-B5-001, Rev. A1 (11/2013)Fig. 3-2, Sample DOCSIS Conguration FileSets Read-Write community string. Set the IP address, netmask and communit
17746-257-B5-001, Rev. A1 (11/2013)3.2 The DOCSIS Conguration File, continued3.2.4 Proprietary Conguration File ‘idhdoc04.cfg’The IDH4 Series will
18746-257-B5-001, Rev. A1 (11/2013)The IDH4 Series will inherit the cable modem community string settings provided by the DOCSIS Conguration File. NO
19746-257-B5-001, Rev. A1 (11/2013)4.0 Web InterfaceOverviewThe IDH4 Series power supply transponder provides an embedded Web server interface to all
PowerAlpha Technologies®
20746-257-B5-001, Rev. A1 (11/2013)Use the following procedure to congure a static IP address on a laptop or computer:1. Click the Start button (low
21746-257-B5-001, Rev. A1 (11/2013)4.0 Web Interface, continued4.1 Local Web Server Access, continuedUse the following procedure to congure a stati
22746-257-B5-001, Rev. A1 (11/2013)4.2 Remote Web Server AccessTo remotely access the IDH4 Series transponder Web server utilizing a Web browser, fol
23746-257-B5-001, Rev. A1 (11/2013)4.3 Navigating the Web PageOnce the Web page has been successfully accessed, the operator is able to select a link
24746-257-B5-001, Rev. A1 (11/2013)4.0 Web Interface, continued4.3 Navigating the Web Page, continued4.3.1 Web Interface Security LevelsWithin the
25746-257-B5-001, Rev. A1 (11/2013)4.0 Web Interface, continued4.4 Verifying Communication ParametersClick the General menu of the web page to displ
26746-257-B5-001, Rev. A1 (11/2013)4.5 Verifying Power Supply and Battery ParametersThe General tab of the Web page also displays the common power su
27746-257-B5-001, Rev. A1 (11/2013)4.7 Viewing HMS Alarm Status via the Web PageHMS alarm levels and currently reported states may be viewed by click
28746-257-B5-001, Rev. A1 (11/2013)4.8 Setting the I/O Controller via the Web PageSettings for the Tamper Switch and I/O Controller may be made by ac
29746-257-B5-001, Rev. A1 (11/2013)4.9 Viewing and Conguring Power Supply Settings via the Web PageConnected power supply parameters may be viewed b
3746-257-B5-001, Rev. A1 (11/2013)AlphaNet™ IDH4 Series DOCSIS® Status Monitor for XM3-HP CableUPS® Technical Manual746-257-B5-001, Rev. A1 Effective
30746-257-B5-001, Rev. A1 (11/2013)4.9 Viewing and Conguring Power Supply Settings via the Web Page, continued4.0 Web Interface, continuedFig. 4-15
31746-257-B5-001, Rev. A1 (11/2013)4.10 Viewing and Conguring Generator Settings via the Web PageWhen a generator is connected to an IDH4X, the gene
32746-257-B5-001, Rev. A1 (11/2013)4.11 Viewing AlphaApps Information via the Web PageThe status of the optional AlphaApp Card may be viewed by navig
33746-257-B5-001, Rev. A1 (11/2013)4.12 Battery ManagementTechnician ID, battery conductance measurements, battery model and battery manufacturing da
34746-257-B5-001, Rev. A1 (11/2013)4.0 Web Interface, continued4.12 Battery Management, continuedClick the drop down menu to view a selection of com
35746-257-B5-001, Rev. A1 (11/2013)Fig. 4-20, System Log Overview4.13 Viewing Power Supply Event and Conguration LogsNavigate to the History menu fo
36746-257-B5-001, Rev. A1 (11/2013)GMT Offset Location Reference+12 Auckland+11 Magadan+10 Sydney+9.5 Adelaide+9 Seoul+8 Hong Kong+7 Bangkok+6.5 Yango
37746-257-B5-001, Rev. A1 (11/2013)4.0 Web Interface, continuedFig. 4-21, Power Supply Event Log4.13 Viewing Power Supply Event and Conguration Log
38746-257-B5-001, Rev. A1 (11/2013)4.0 Web Interface, continuedFig. 4-22, Power Supply Conguration Log4.13 Viewing Power Supply Event and Congurat
39746-257-B5-001, Rev. A1 (11/2013)4.0 Web Interface, continued4.14 Battery Event LogThe Battery Event Log can be accessed by navigating to the Hist
4746-257-B5-001, Rev. A1 (11/2013)ContentsSafety Notes ...
40746-257-B5-001, Rev. A1 (11/2013)4.15 Viewing the Modem Event Log via the Web PageThe transponder's event log may be viewed using a Web browse
41746-257-B5-001, Rev. A1 (11/2013)4.0 Web Interface, continued4.16 RF Constellation PageSelect the Tools menu to access the Constellation page. Cli
42746-257-B5-001, Rev. A1 (11/2013)4.0 Web Interface, continued4.16 RF Constellation Page, continuedControls:• Run — Start the sampling of data by p
43746-257-B5-001, Rev. A1 (11/2013)4.0 Web Interface, continued4.18 MicroreectionsSelect the "Tools" menu to access the Microreections p
44746-257-B5-001, Rev. A1 (11/2013)5.1 Upgrading IDH4 Series Modem FirmwareThe rmware is upgraded using standard DOCSIS methods as dened in RFC4639
45746-257-B5-001, Rev. A1 (11/2013)5.1.3 Upgrading Manually by Setting SNMP Parameters1. Acquire the rmware and CVC les for your IDH4 Series from A
46746-257-B5-001, Rev. A1 (11/2013)6.1 SCTE-HMS MIBs The IDH4 Series remotely reports power supply data and alarms using the Simple Network Managemen
47746-257-B5-001, Rev. A1 (11/2013)6.2 SCTE-HMS MIB Alarms6.2.1 SCTE-HMS Congurable AlarmsBinary to Hex Conversions for Alarm SettingsUnused HiHi H
48746-257-B5-001, Rev. A1 (11/2013)6.2.1 SCTE-HMS Congurable Alarms, continuedTable 6-3, Recommended Settings for IDH4 Series Analog Alarms Analog A
49746-257-B5-001, Rev. A1 (11/2013)6.0 Data Management, continuedDiscrete Alarms Description SettingpsInverterStatus (1) Inverter OFF DisablepsInvert
5746-257-B5-001, Rev. A1 (11/2013)Contents, continued6.2.3 General Power Supply Alarms ...
50746-257-B5-001, Rev. A1 (11/2013)6.2.2 SNMP TrapsUse of SNMP Traps allow the network manager to set conditions (alarms) under which the device (or
51746-257-B5-001, Rev. A1 (11/2013)6.0 Data Management, continued6.2.2 SNMP Alarm Traps, continuedTrap on NormalThe IDH4 Series has the capability o
52746-257-B5-001, Rev. A1 (11/2013)6.2.3 General Power Supply AlarmsThe Intelligent CableUPS detects a wide array of alarms and displays the type of
53746-257-B5-001, Rev. A1 (11/2013)6.2.3 General Power Supply Alarms, continuedActive Alarm Alarm type Alarm Category Probable Cause of Alarm Correct
54746-257-B5-001, Rev. A1 (11/2013)Table 6-7, Battery Alarms: Classications, Causes and Corrections6.2.4 Battery AlarmsThe Intelligent CableUPS dete
55746-257-B5-001, Rev. A1 (11/2013)6.0 Data Management, continuedAccompanying the release of the IDH4 Series are new MIB les. These are backward-com
56746-257-B5-001, Rev. A1 (11/2013)6.3 The Alpha MIBs, continuedThe Alpha MIB is dened within the enterprises branch of the MIB tree starting at 1.3
57746-257-B5-001, Rev. A1 (11/2013)6.3 The Alpha MIBs, continued 6.3.1 The Alpha MIB StructureMeasurements and settings for the power supply, genera
58746-257-B5-001, Rev. A1 (11/2013)7.1 Verifying Power Supply Device Address Before installing the hardware, provision the DHCP server with the cable
59746-257-B5-001, Rev. A1 (11/2013)Captive Screws7.2 Installation / Replacement Procedure in XM3-HP Power SuppliesIf the XM3-HP CableUPS has been shi
6746-257-B5-001, Rev. A1 (11/2013)FiguresFig. 1-1, AlphaNet IDH4X ...
60746-257-B5-001, Rev. A1 (11/2013)7.2 Module Installation Procedure in XM3-HP Power Supplies, continued7. Fasten the IDH4 Series to the Inverter Mo
61746-257-B5-001, Rev. A1 (11/2013)7.3 IDH4X LEDs and ConnectionsFig. 7-4, IDH4X LEDs and ConnectorsItem LED or Connector Status Behavior Indication1
62746-257-B5-001, Rev. A1 (11/2013)Item LED or Connector Status Behavior Indication1ALM/RDY: Alarm and ReadyN/A OFF No power or malfunctioning transpo
63746-257-B5-001, Rev. A1 (11/2013)7.5 IDH4L LEDs and ConnectionsItem LED or Connector Status Behavior Indication1ALM/RDY: Alarm and ReadyN/A OFF No
64746-257-B5-001, Rev. A1 (11/2013)Fig. 7-8, System Interconnection Diagram7.7 Front Panel ConnectionsConnectionsConnections with more than one power
65746-257-B5-001, Rev. A1 (11/2013)7.8 Environmental ConnectionsThe IDH4X and IDH4L have the capability to monitor and control enclosure environmenta
66746-257-B5-001, Rev. A1 (11/2013)7.9 Environmental Control MIBs atiMgmtSysTempCtrl (1.3.6.1.4.1.926.1.3.2.4.1)Value list Descriptionoff(1) Temperat
67746-257-B5-001, Rev. A1 (11/2013)atiMgmtSysTempTemperature (1.3.6.1.4.1.926.1.3.2.4.5)Size list Description1...70 Thermostatic temperature setpoint
68746-257-B5-001, Rev. A1 (11/2013)Set these OIDs to the specied value FunctionalityatiMgmtSysTempTemperature (1.3.6.1.4.1.926.1.3.2.4.5) to 5 Heater
69746-257-B5-001, Rev. A1 (11/2013)8.1 36V Single and Dual StringsFig. 8-1, 36V System, Single StringSense Wire Kits:Alpha P/N: 874-842-21 (6')A
7746-257-B5-001, Rev. A1 (11/2013)Safety NotesReview the drawings and illustrations contained in this manual before proceeding. If there are any quest
70746-257-B5-001, Rev. A1 (11/2013)9.1 Initial Start Up and Local VericationTo conrm successful hardware installation before leaving the installati
71746-257-B5-001, Rev. A1 (11/2013)Fig. 9-2, General Tab Screen9.0 Start Up and Verication, continued9.1 Initial Start Up and Local Verication, co
72746-257-B5-001, Rev. A1 (11/2013)9.2 Verifying Correct Hardware InterconnectionThe BAT A/B and BAT C/D LED indicators on the front panel of the IDH
73746-257-B5-001, Rev. A1 (11/2013)Fig. 9-4, LED Functionality and Indications9.3 System Status Indicators and Reset ButtonThe IDH4 Series indicates
74746-257-B5-001, Rev. A1 (11/2013)9.3.1 Detailed LED Descriptions, continuedREG - CM RegistrationThis LED blinks while the modem registers with the
75746-257-B5-001, Rev. A1 (11/2013)Conguring the Rx/Tx Power LED - Custom SettingsIf desired, the RF Power Level ranges for the Rx/Tx PWR LED may be
76746-257-B5-001, Rev. A1 (11/2013)10.1 Denitions and SettingsThe following tables display commonly-congured Alpha MIB parameters and provide speci
77746-257-B5-001, Rev. A1 (11/2013)10.1 Denitions and Settings, continuedParameter OID Description Access Type ValueCOMMUNITY STRINGS atiMgmtSnmpC
78746-257-B5-001, Rev. A1 (11/2013)10.1 Denitions and Settings, continuedParameter OID Description Access Type ValueENVIRONMENTAL MANAGERatiMgmtSysT
79746-257-B5-001, Rev. A1 (11/2013)Parameter OID Description Access Type ValueENVIRONMENTAL CONTROL CONNECTOR, continuedatiMgmtSysIOSysIOPinCtrl 1.3.6
8746-257-B5-001, Rev. A1 (11/2013)The AlphaNet IDH4 Series Embedded DOCSIS Transponder allows monitoring of Alpha power supplies through existing cabl
80746-257-B5-001, Rev. A1 (11/2013)Parameter OID Description Access Type ValueSYSTEM COUNTERSatiBBSysViewCounters 1.3.6.1.4.1.926.1.4.1.1.4 Object Ide
81746-257-B5-001, Rev. A1 (11/2013)10.1 Denitions and Settings, continued10.0 Alpha MIB Parameters, continuedParameter OID Description Access Type V
82746-257-B5-001, Rev. A1 (11/2013)10.1 Denitions and Settings, continued10.0 Alpha MIB Parameters, continuedParameter OID Description Access Type V
83746-257-B5-001, Rev. A1 (11/2013)11.0 SpecicationsIDH4X IDH4 IDH4LBattery MonitoringUp to four strings of 36 or 48V batteries (6V batts congurable
84746-257-B5-001, Rev. A1 (11/2013)IDH4X IDH4 IDH4LPower Supply Monitored ParametersMajor AlarmAggregate alarm consisting of: Test fail, battery fail,
85746-257-B5-001, Rev. A1 (11/2013)Acronym DenitionsANSI: American National Standards InstituteBER: Basic Encoding RulesCM: Cable ModemCMTS: Cabl
86746-257-B5-001, Rev. A1 (11/2013)13.0 Dual IP Mode (Addendum)13.1 OverviewThe IDH4 Series can operate in either Single (default) or Dual IP mode. In
87746-257-B5-001, Rev. A1 (11/2013)Fig. 13-3, Single IP IDH4 Series Web Page(partial page only; data values shown for illustration purposes only)13.0
88746-257-B5-001, Rev. A1 (11/2013)The CPE Transponder IP can be assigned its IP, Subnet Mask and Gateway Addresses via a DHCP server.13.0 Dual IP Mo
89746-257-B5-001, Rev. A1 (11/2013)13.0 Dual IP Mode (Addendum), continued13.3 Conguring Dual IP Mode, continued13.3.1 idhdoc04.cfg in Dual IP Mod
9746-257-B5-001, Rev. A1 (11/2013)Fig. 1-4, Side View, AlphaNet IDH4 SeriesRF Connector1.0 Introduction, continuedIntelligent CableUPS Interface (lo
90746-257-B5-001, Rev. A1 (11/2013)13.0 Dual IP Mode (Addendum), continued13.3 Conguring Dual IP Mode, continued13.3.3 Specifying idhdoc04.cfg nam
91746-257-B5-001, Rev. A1 (11/2013)13.0 Dual IP Mode (Addendum), continued13.4 Dual IP SNMP Community StringsThe transponder community strings used
92746-257-B5-001, Rev. A1 (11/2013)13.0 Dual IP Mode (Addendum), continued13.5 Security in Dual IP Mode, continued Method 2: Dual IP Security Using
this page intentionally blank
Visit us at www.alpha.com Due to continuing product development, Alpha Technologies reserves the right to change specications without notice. Copyrig