2.3 Wall-mount Installations
The wall-mount version is equipped with an adaptor bracket allowing the APC or
APL pole-mount enclosure to be mounted on a flat, vertical surface.
NOTE: BEFORE INSTALLING THE MTA, ENSURE THAT ALL OPTIONS HAVE
BEEN INSTALLED AND PROPERLY CONNECTED. REFER TO SECTION 2.11
OPTIONS, FOR INSTALLATION PROCEDURES.
Procedure:
1. Mount the wall-mount bracket to a flat vertical surface. The mounting area
should be located directly in front of a wall stud (2 x 4; 2 x 6; etc.). If such
an area is not possible, appropriate anchors and lag bolts must be used.
Mount the bracket by first marking the location for the holes, using the
bracket as a template (the distance between the holes is 4.5” c-c).
2. Drill out the holes using a 1/4” drill bit. Mount the bracket to the wall using
two (2) 3/8” x 1.5” long steel lag bolts and washers. Make certain that the
1/4-20 (Phillips) screw is located in the upper right-hand side of the bracket
before securing it to the wall.
3. Mount the enclosure to the wall bracket by fitting the slots (in the APC or
APL enclosure bracket) over the rivets in the wall bracket. The enclosure’s
bracket fits on the outside of the wall bracket.
Tighten the screw located on
the upper-right corner of the wall bracket using a #2 Phillips head
screwdriver.
4. Install the Modular Transformer Assembly (MTA) onto the baseplate, (see
section 2.9 MODULAR TRANSFORMER ASSEMBLY).
Photo 2.3.b Photo 2.3.c
Align Slots with
rivets and Screw
2. INSTALLATION
11
1/4-20 Screw
(upper-right hand side)
Wall Mounting Holes
Photo 2.3.a
Wall Mount Bracket
Tighten Screw